This is an old revision of the document!
Table of Contents
0k Freezer Monitoring Manual
Grafana dashboard
You can visit the Grafana dashboard at https://grafana.xnorit.be
Select a panel to view in the “0K_FreezerMonitoring” folder, as shown in the image.
'All' vs 'Light' vs 'Full' panels
Light panels:
A panel named with 'Light' provides the user with a quick and simple to read overview, with the drawback that it only contains an limited amount of data and information.
Each monitored freezers is provided with a small indication of the current temperature. Beneath the temperature is a small chart visible. If a temperature is out of range (As seen for freezer T_209), both temperature and chart change color.
The default color setting is:
- temperature below -100 = Blue
- temperature in-between -100 and -60 = Green
- temperature in-between -60 and -50 = Orange
- temperature in-between -50 = Red
Below the temperatures there is a field visible containing “Freezer health”. If a freezer supports this function, the freezer health will detect interruptions in freezer operation (breakdown/failure/AC loss). Using the default settings, this detection happens within 1 minute. The shown percentage is a calculated average over the selected time-span inside Grafana, see <color #ed1c24>panel settings</color> for more information.
Full panels:
A panel named with 'Full' provides a more thorough overview of each recorded freezer data, with the drawback of lessened readability.
At the left an 'alert overview' is visible, providing an direct overview on freezers with possible issues.
The charts contain following information:
- Freezer health (purple/pink)
- Room temperature (Orange) (Measured within the monitor enclosure resulting in a ~5°C increase in temperature).
- Freezer temperature (Blue)
- Mail alert threshold (Red)
All panels:
A panel named 'ALL' contains a 'Light' representation of all connected freezers at a given site.